Answers | Verified And Well Detailed Answers |
Plus Rationales | Guaranteed Pass | Latest Exam
Update
Question 1:
A Utah HVAC contractor is calculating the cooling load for a residence. One ton of
nominal cooling capacity equals approximately how many Btu/h?
A. 8,000 Btu/h
B. 10,000 Btu/h
C. 12,000 Btu/h
D. 15,000 Btu/h
answer: C
Rationale:
One ton of cooling capacity is defined as 12,000 Btu/h. This is the standard conversion
used when sizing equipment based on a calculated load .
Question 2:
A contractor is installing a Category IV condensing furnace. Which venting characteristic
is most critical when selecting the vent system?
A. The vent must be constructed from unlined masonry.
B. The vent must rely exclusively on natural draft.
C. The vent must be listed and approved for positive-pressure, condensing flue-gas
conditions.
D. The vent must be larger than the manufacturer's specified diameter.
answer: C
Rationale:
Category IV appliances operate with positive vent pressure and produce cool, moisture-
,laden combustion products. The vent material must be specifically listed and approved
for these conditions to resist corrosion and condensate .
Question 3:
During commissioning of a split-system heat pump, the contractor measures abnormally
high superheat, low suction pressure, and relatively normal-to-low head pressure. Which
condition is most consistent with these readings?
A. Overcharge of refrigerant
B. Refrigerant undercharge
C. Excessive indoor airflow
D. Noncondensable gas in the system
answer: B
Rationale:
An undercharged system has insufficient liquid refrigerant reaching the evaporator. This
produces low suction pressure and high evaporator superheat because the refrigerant
boils off early. High superheat combined with low suction pressure is a classic indication
to investigate charge level and leaks .
Question 4:
A furnace manufacturer specifies a temperature rise of 35°F to 65°F. During
commissioning, the measured temperature rise is 78°F with the blower at the specified
heating speed. What should the contractor investigate first?
A. Increase the gas pressure immediately.
B. Increase the furnace input above the nameplate rating.
C. Investigate inadequate airflow or excessive system resistance.
D. Reduce the return-air temperature artificially.
answer: C
Rationale:
A temperature rise above the manufacturer's specified range indicates insufficient
airflow across the heat exchanger. Possible causes include a dirty filter, restrictive
,ductwork, closed dampers, or incorrect blower setup. Increasing gas input would worsen
the overheating condition .
Question 5:
Which condition most directly increases the sensible cooling load of a building?
A. Reduced outdoor-air ventilation
B. Increased insulation thickness
C. Increased solar heat gain through glazing
D. Reduced lighting wattage
answer: C
Rationale:
Solar radiation entering through windows adds sensible heat to the conditioned space
and increases the required cooling capacity .
Question 6:
A heat pump operates in cooling mode, but the indoor coil begins icing while indoor
airflow is confirmed adequate. Which condition should be investigated first?
A. Excessively high indoor humidity only
B. Low refrigerant charge or restricted refrigerant flow
C. Oversized outdoor fan
D. Excessive condenser airflow
answer: B
Rationale:
Insufficient refrigerant or a restriction can reduce evaporator pressure and temperature
enough to cause coil icing. Adequate airflow rules out airflow as the primary cause .
, Question 7:
Which component reverses refrigerant flow in a typical air-source heat pump?
A. Accumulator
B. Compressor
C. Four-way reversing valve
D. Thermal expansion valve
answer: C
Rationale:
The reversing valve changes the direction of refrigerant flow so the indoor and outdoor
coils exchange their heating and cooling functions .
Question 8:
What is the primary purpose of Manual J in residential HVAC design?
A. Selecting refrigerant piping sizes
B. Calculating residential heating and cooling loads
C. Designing electrical branch circuits
D. Determining gas-pipe pressure
answer: B
Rationale:
Manual J is used to determine the design heating and cooling loads needed for
residential equipment sizing .
Question 9:
A duct system has excessive static pressure and inadequate airflow at several supply
registers. Which condition is most likely contributing to the problem?
A. Oversized return ductwork
B. Excessively restrictive ductwork
C. Low outdoor temperature
D. High condenser airflow