ARE CLASS 2 REMOTE - CONTROL cables permitted to be
STRAPPED or otherwise attached to RACEWAYS for support ?
A) No, this is prohibited
B) Yes, if the raceway is supported properly according to the NEC
C) Yes, if the raceway is not flexible but rigid, such as rigid metal
conduit, electrical metallic tubing, etc.
D) Yes, if the raceway contains power supply conductors for equipment
which the class 2 circuit conductors control - ANSWER-No, this is
prohibited
article 725.143
Where flexible cord is connected to the building ceiling with a suitable "
tension take - up device" the maximum length of the cord from the
supply joint to the take - up device is _____________ feet.
,2|Page
A) 2
B) 4
C) 6
D) 8 - ANSWER-6
article 368.56 (B) (2)
All of the following WIRING METHODS are permitted in a ceiling
space used as a return - air plenum except:
A) IMC
B) NMC
C) EMT
D) MI CABLE - ANSWER-NMC
article 300.22 (B)
Excluding exceptions, nonmetallic sheathed cable is permitted in all of
the following areas EXECPT: - ANSWER-Above a suspended ceiling of
a retail store
article 334.12 (A) (2)
, 3|Page
The NEC permits 3/8 - inch FLEXIBLE METAL CONDUIT to be
unsupported for tap connection to light fixtures, provided the length
doses not exceed __________ feet. - ANSWER-6
article 348.20 (2) (C)
What is the maximum spacing between supports, in ft., for 3/4 - inch,
rigid nonmetallic conduit? - ANSWER-3
table 352.30
Are single conductors with UF insulation permitted to be direct - buried
? - ANSWER-Yes , when all conductors are run in the same trench
article 300.5
Threadless fittings used with RIGID METAL CONDUCT installed in a
WET LOCATION shall be : - ANSWER-Listed for use in wet locations
The minimum width of clear WORKING SPACE required for a 24- inch
wide electrical panel supplied by 240/120 - volt supply is _______
inches. - ANSWER-30