Mass Oil burner / NFPA 31 & NORA Comprehensive Frequently Tested Questions With Verified Multiple Choice and Conceptual Actual 100% Correct Detailed Answers Guaranteed Pass!!Current Update!! 1. The trial for ignition period for oil burners less than 20 GPM is? - ANSWER 15 seconds 2. Fusible switches shall operate at a temp of - ANSWER 165F 3. A masonry chimney needs a metal liner - ANSWER False 4. Any valves used on oil burner installation must be a - ANSWER Fusible valve 5. What form is used to pull an oil burner permit - ANSWER Form 1 6. What size pipe is used to cross connect tank outlet piping - ANSWER 1/2 inch 7. What is an oil safety valve required - ANSWER On existing installations when a burner, boiler, furnace or tank is replaced 8. When must you install a draft regulator - ANSWER When not exempted by the manufacturer 9. As of January 1 2014, max safety timing for an oil burner safety switch must be no more than - ANSWER 15 seconds

Mostrar más Leer menos
Institución
NORA Oil Heat
Grado
NORA Oil Heat










Ups! No podemos cargar tu documento ahora. Inténtalo de nuevo o contacta con soporte.

Escuela, estudio y materia

Institución
NORA Oil Heat
Grado
NORA Oil Heat

Información del documento

Subido en
22 de diciembre de 2025
Número de páginas
29
Escrito en
2025/2026
Tipo
Examen
Contiene
Preguntas y respuestas

Vista previa del contenido

Mass Oil burner / NFPA 31 & NORA 2026-2027
Comprehensive Frequently Tested Questions
With Verified Multiple Choice and Conceptual
Actual 100% Correct Detailed Answers

Guaranteed Pass!!Current Update!!


1. The trial for ignition period for oil burners less than 20 GPM is? - ANSWER
15 seconds



2. Fusible switches shall operate at a temp of - ANSWER 165F



3. A masonry chimney needs a metal liner - ANSWER False



4. Any valves used on oil burner installation must be a - ANSWER Fusible
valve



5. What form is used to pull an oil burner permit - ANSWER Form 1



6. What size pipe is used to cross connect tank outlet piping - ANSWER 1/2
inch



7. What is an oil safety valve required - ANSWER On existing installations
when a burner, boiler, furnace or tank is replaced

,8. When must you install a draft regulator - ANSWER When not exempted
by the manufacturer


9. As of January 1 2014, max safety timing for an oil burner safety switch must
be no more than - ANSWER 15 seconds



10.What type of boiler must be equipped with low water cut off - ANSWER
Water boilers over 400,000 BTU, all steam boiler



11.What device must be equipped with air proving switch - ANSWER A
draft inducer



12.New burner controls must be - ANSWER Interrupted ignition



13.Hot water boilers need low water cut off if over - ANSWER 500,000 BTU


14.How far must continuous concrete slab extend beyond tank perimeter -
ANSWER 8 inches



15.Can I use any form other than form 1 or form 1A - ANSWER No, only
form 1 and 1A are approved by state fire Marshall

, 16.What must I do if I have a oil tank larger than 10,000 gallons - ANSWER
You must apply for, and obtain both a permit and license from the local
town or city for the use of the tank


17.What license are acceptable for installing an oil burner or oil tank - ANSWER
M.G.L c. 148, & 10D, and applicable provisions of St. 1964, C. 680 allows
for only the holder of certificate of competency to install oil burner
equipment and sign form 1A


18.Do I need to pull a permit when replacing an oil line or installing an osv -
ANSWER Yes. Any alteration of oil burner install requires a permit be
pulled under CMR 1.00 using form 1 only



19.Can I cross connect two tanks at bottom with 3/8 pipe tubing - ANSWER
No, cross connecting must be made with no smaller than 1/2 inch iron pipe
or o.d. Tubing


20.On a new install, can I install an OSV in the supply line instead of enasing
the line - ANSWER No, on new installs where the supply line is in direct
contact with concrete or earth, the supply line must be in a sleeve


21.Is any non metallic material acceptable for use as an oil line sleeve? Would
pvc hose be allowed - ANSWER Yes



22.When can I use an oil safety valve - ANSWER On existing installations
when a burner, boiler, furnace or tank is replaced
$13.49
Accede al documento completo:

100% de satisfacción garantizada
Inmediatamente disponible después del pago
Tanto en línea como en PDF
No estas atado a nada

Conoce al vendedor

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
EWLindy Chamberlain College Of Nursing
Ver perfil
Seguir Necesitas iniciar sesión para seguir a otros usuarios o asignaturas
Vendido
703
Miembro desde
3 año
Número de seguidores
431
Documentos
7331
Última venta
5 días hace
EN.CY.CLO.PE.DI.A

Hello, I am Passionate about education with over 7yrs teaching.. Welcome to my page...my documents are 100% guaranteed to help you Ace in your career path, Combining a wide view of career courses education Journey Proffesionaly. Will be very helpful for those students who want to make a change in nursing field and other close courses . Please go through the sets description appropriately before any purchase. The *Sets have been used years in years out by serious students to exercise, revise and even pass through their examinations. All revisions done by Expert Minds. This Gives You No Excuse To Leave A Bad Review. Thankyou . SUCCESS IN YOUR EDUCATION JOURNEY !! GOODLUCK IN YOUR STUDIES.

Lee mas Leer menos
3.8

105 reseñas

5
54
4
13
3
15
2
6
1
17

Recientemente visto por ti

Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes