answers
Where Public Mode audible appliances are installed they
|\ |\ |\ |\ |\ |\ |\ |\
shall be ____________ above average ambient sound level -
|\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔15dba
|\ |\ |\
Where audible appliances are installed in mechanical
|\ |\ |\ |\ |\ |\ |\
equipment rooms, the average ambient sound level is -|\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔85dba |\ |\
An average ambient sound level greater than ______ shall
|\ |\ |\ |\ |\ |\ |\ |\ |\
require the use of a visible notification appliance -
|\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔105dba |\ |\
All fire detection devices shall be listed or approved for
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
the purpose for which they are intended - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔True |\
A detector should not be recessed in any way unless they
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
have been tested for such a mounting - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔True |\
,How far from the doorway shall a Manual fire alarm
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
station be mounted - CORRECT ANSWERS ✔✔5'
|\ |\ |\ |\ |\ |\
Vane type flow switch have no longer than _____ to initiate
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
alarm - CORRECT ANSWERS ✔✔90 sec
|\ |\ |\ |\ |\ |\
smoke detectors must be tested every - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔1 year |\ |\
Sensitivity in smoke detectors and single & multiple-
|\ |\ |\ |\ |\ |\ |\
station smoke alarms in other than 1&2 family dwellings
|\ |\ |\ |\ |\ |\ |\ |\ |\
shall be checked within _____ year or years after
|\ |\ |\ |\ |\ |\ |\ |\ |\
installation - CORRECT ANSWERS ✔✔1 year |\ |\ |\ |\ |\
A spot-type heat detector located on a wall shall not be
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
more than _____ inches from the ceiling - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔12'' |\
With a peak ceiling, heat and smoke detectors shall be
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
located within _____ of the peak, measured horizontally -
|\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔36'' |\ |\
smoke detectors shall not be located near - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔Air supply diffusers |\ |\ |\
, When beams project more than _____ inches below the
|\ |\ |\ |\ |\ |\ |\ |\ |\
ceiling and are more than 8' on center, each bay formed
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
by the beams shall be treated as a separate area for heat
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
detectors - CORRECT ANSWERS ✔✔18'' |\ |\ |\ |\
When manual fire alarm boxes are used, the distance
|\ |\ |\ |\ |\ |\ |\ |\ |\
between boxes will not be in excess of - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔200' |\
A water flow device should be field adjusted so that an
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
alarm is initiated in no more than _____ seconds -
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
CORRECT ANSWERS ✔✔90 seconds |\ |\ |\
smoke detectors shall not be located directly in the air
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\
stream of - CORRECT ANSWERS ✔✔supply registers
|\ |\ |\ |\ |\ |\
Detectors shall not be installed until after - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔Final clean up of all trades |\ |\ |\ |\ |\ |\
a heat detector integrally mounted on a smoke detector
|\ |\ |\ |\ |\ |\ |\ |\ |\
shall be listed and approved for not less than - CORRECT
|\ |\ |\ |\ |\ |\ |\ |\ |\ |\ |\
ANSWERS ✔✔50' |\