◉Minimum distance for raceways under metal roof decking . Ans: 1.5
Inches.
◉R=E/I . Ans: Ohms Law.
◉Maximum recess for a box in a wall . Ans: ¼ inch.
◉Minimum size copper equipment grounding conductor for 60 AMP
device . Ans: 10 AWG.
◉PV circuits enclosure requirement . Ans: The PV system dc circuits are
separated from other circuits by a barrier or partition.
, ◉Resistance augmentation for ground rod electrode . Ans: The
resistance shall be augmented by one additional electrode if the
resistance is not 25 Ohms or less.
◉Outlet placement near a pool . Ans: The outlet shall not be placed
within 5 feet of the inside wall nor 5 feet of the tidal high water mark.
◉3-phase transformer connection . Ans: Delta.
◉Minimum size copper supply side bonding jumper for 3/0 AWG
conductors . Ans: 4 AWG.
◉Circular mill . Ans: A unit used in electrical trades to indicate the
cross-sectional area of wires.
◉Minimum rating for feeder disconnecting means for single family
dwelling . Ans: 100 amps.
◉Motor controller marking requirements . Ans: Motor controllers are
required to be marked with the voltage, the current or horsepower rating,
the short-circuit current rating.
◉Minimum spacing for supplement electrodes . Ans: 6 Feet.