What is a sprinkler system? - Correct answer ✔A fire extinguishing system,
|! |! |! |! |! |! |! |! |! |! |! |!
other than a mist fire extinguishing system that utilizes water as the
|! |! |! |! |! |! |! |! |! |! |! |!
extinguishing agent |!
How long must a detailed record be kept? - Correct answer ✔Minimum 3
|! |! |! |! |! |! |! |! |! |! |! |! |!
years
How often are sprinklers subject to a hydrostatic pressure test? - Correct
|! |! |! |! |! |! |! |! |! |! |! |!
answer ✔At least once every 5 years
|! |! |! |! |! |!
Who's responsible for maintaining the sprinkler system? - Correct answer
|! |! |! |! |! |! |! |! |! |!
✔Owner
Under what conditions should the FD be notified if a sprinkler system is
|! |! |! |! |! |! |! |! |! |! |! |! |!
OOS? - Correct answer ✔- sprinkler out of service on more than 1 floor of a
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
building
- work cannot be completed and system restored within 8 hours
|! |! |! |! |! |! |! |! |! |!
-one or more fire protection services are out of service at the same time
|! |! |! |! |! |! |! |! |! |! |! |! |!
,If no impairment is found: - Correct answer ✔Green tag placed on main
|! |! |! |! |! |! |! |! |! |! |! |! |!
control valve |!
If a system is fully out of service what color disc should be placed on the FD
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
connection? - Correct answer ✔White |! |! |! |!
If a system is partially out of service what color disc should be placed on the
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
FD connection? - Correct answer ✔Blue
|! |! |! |! |!
What color tag should be placed on the main control valve if a system if fully
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
or partially out of service? - Correct answer ✔Red
|! |! |! |! |! |! |! |!
What should the red tag on a main control valve indicate? - Correct answer
|! |! |! |! |! |! |! |! |! |! |! |! |! |!
✔Sprinkler company name, date of removal from service, and anticipated
|! |! |! |! |! |! |! |! |! |!
return to service date |! |! |!
Before authorizing the placing of the fire protection out of service the
|! |! |! |! |! |! |! |! |! |! |! |!
impairment coordinator shall: - Correct answer ✔• Notify the Certificate of
|! |! |! |! |! |! |! |! |! |! |!
Fitness holder responsible for supervising the maintenance of the standpipe
|! |! |! |! |! |! |! |! |! |!
system, sprinkler system or fire alarm system.
|! |! |! |! |! |!
• Determine the extent and expected duration of the out-of-service condition.
|! |! |! |! |! |! |! |! |! |!
• Inspect the areas or buildings involved and assess the increased risks. Make
|! |! |! |! |! |! |! |! |! |! |! |! |!
appropriate recommendations to the owner. |! |! |! |!
• Notify the Fire Department in accordance with FC 901.7.5, if required.
|! |! |! |! |! |! |! |! |! |! |!
• Notify the responsible person designated by the owner to issue hot work
|! |! |! |! |! |! |! |! |! |! |! |! |!
authorizations in accordance with FC Chapter 26. |! |! |! |! |! |!
, • Notify the central station and insurance carrier.
|! |! |! |! |! |! |!
• Notify the occupants in the affected areas if the duration of time the
|! |! |! |! |! |! |! |! |! |! |! |! |! |!
sprinkler system or fire alarm system will be out of service is estimated to be
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
more than 30 minutes.
|! |! |!
• Place a tag at each fire department connection, standpipe and sprinkler
|! |! |! |! |! |! |! |! |! |! |! |!
system control valve and fire command center, indicating which fire
|! |! |! |! |! |! |! |! |! |!
protection system, or part thereof, is out of service. |! |! |! |! |! |! |! |!
• Maintain the fire protection system in service until work is ready to begin.
|! |! |! |! |! |! |! |! |! |! |! |! |!
Who is authorized to place a tag on a system? - Correct answer ✔- master fire
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
suppression piping contractor
|! |! |!
- FDNY
|!
- owner
|!
- master plumber (as restricted)
|! |! |! |!
What are the approved non freezing solutions for a sprinkler? - Correct
|! |! |! |! |! |! |! |! |! |! |! |!
answer ✔- glycerin not greater than 48%
|! |! |! |! |! |!
- propane glycol not greater than 38%
|! |! |! |! |! |!
What is a riser card? - Correct answer ✔Approved card baring dates of each
|! |! |! |! |! |! |! |! |! |! |! |! |! |!
inspection, COF # and COF signature |! |! |! |! |!
Where should the riser card be posted? - Correct answer ✔On the premises
|! |! |! |! |! |! |! |! |! |! |! |! |!
near the main water supply control valve
|! |! |! |! |! |!
accur ate detailed solutions |! |!
What is a sprinkler system? - Correct answer ✔A fire extinguishing system,
|! |! |! |! |! |! |! |! |! |! |! |!
other than a mist fire extinguishing system that utilizes water as the
|! |! |! |! |! |! |! |! |! |! |! |!
extinguishing agent |!
How long must a detailed record be kept? - Correct answer ✔Minimum 3
|! |! |! |! |! |! |! |! |! |! |! |! |!
years
How often are sprinklers subject to a hydrostatic pressure test? - Correct
|! |! |! |! |! |! |! |! |! |! |! |!
answer ✔At least once every 5 years
|! |! |! |! |! |!
Who's responsible for maintaining the sprinkler system? - Correct answer
|! |! |! |! |! |! |! |! |! |!
✔Owner
Under what conditions should the FD be notified if a sprinkler system is
|! |! |! |! |! |! |! |! |! |! |! |! |!
OOS? - Correct answer ✔- sprinkler out of service on more than 1 floor of a
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
building
- work cannot be completed and system restored within 8 hours
|! |! |! |! |! |! |! |! |! |!
-one or more fire protection services are out of service at the same time
|! |! |! |! |! |! |! |! |! |! |! |! |!
,If no impairment is found: - Correct answer ✔Green tag placed on main
|! |! |! |! |! |! |! |! |! |! |! |! |!
control valve |!
If a system is fully out of service what color disc should be placed on the FD
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
connection? - Correct answer ✔White |! |! |! |!
If a system is partially out of service what color disc should be placed on the
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
FD connection? - Correct answer ✔Blue
|! |! |! |! |!
What color tag should be placed on the main control valve if a system if fully
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
or partially out of service? - Correct answer ✔Red
|! |! |! |! |! |! |! |!
What should the red tag on a main control valve indicate? - Correct answer
|! |! |! |! |! |! |! |! |! |! |! |! |! |!
✔Sprinkler company name, date of removal from service, and anticipated
|! |! |! |! |! |! |! |! |! |!
return to service date |! |! |!
Before authorizing the placing of the fire protection out of service the
|! |! |! |! |! |! |! |! |! |! |! |!
impairment coordinator shall: - Correct answer ✔• Notify the Certificate of
|! |! |! |! |! |! |! |! |! |! |!
Fitness holder responsible for supervising the maintenance of the standpipe
|! |! |! |! |! |! |! |! |! |!
system, sprinkler system or fire alarm system.
|! |! |! |! |! |!
• Determine the extent and expected duration of the out-of-service condition.
|! |! |! |! |! |! |! |! |! |!
• Inspect the areas or buildings involved and assess the increased risks. Make
|! |! |! |! |! |! |! |! |! |! |! |! |!
appropriate recommendations to the owner. |! |! |! |!
• Notify the Fire Department in accordance with FC 901.7.5, if required.
|! |! |! |! |! |! |! |! |! |! |!
• Notify the responsible person designated by the owner to issue hot work
|! |! |! |! |! |! |! |! |! |! |! |! |!
authorizations in accordance with FC Chapter 26. |! |! |! |! |! |!
, • Notify the central station and insurance carrier.
|! |! |! |! |! |! |!
• Notify the occupants in the affected areas if the duration of time the
|! |! |! |! |! |! |! |! |! |! |! |! |! |!
sprinkler system or fire alarm system will be out of service is estimated to be
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
more than 30 minutes.
|! |! |!
• Place a tag at each fire department connection, standpipe and sprinkler
|! |! |! |! |! |! |! |! |! |! |! |!
system control valve and fire command center, indicating which fire
|! |! |! |! |! |! |! |! |! |!
protection system, or part thereof, is out of service. |! |! |! |! |! |! |! |!
• Maintain the fire protection system in service until work is ready to begin.
|! |! |! |! |! |! |! |! |! |! |! |! |!
Who is authorized to place a tag on a system? - Correct answer ✔- master fire
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
suppression piping contractor
|! |! |!
- FDNY
|!
- owner
|!
- master plumber (as restricted)
|! |! |! |!
What are the approved non freezing solutions for a sprinkler? - Correct
|! |! |! |! |! |! |! |! |! |! |! |!
answer ✔- glycerin not greater than 48%
|! |! |! |! |! |!
- propane glycol not greater than 38%
|! |! |! |! |! |!
What is a riser card? - Correct answer ✔Approved card baring dates of each
|! |! |! |! |! |! |! |! |! |! |! |! |! |!
inspection, COF # and COF signature |! |! |! |! |!
Where should the riser card be posted? - Correct answer ✔On the premises
|! |! |! |! |! |! |! |! |! |! |! |! |!
near the main water supply control valve
|! |! |! |! |! |!